| Hubbell Wiring Device-Kellems Product
Specifications |
| Product Type |
Watertight IEC 309 |
| Body Style |
Straight |
| Material |
Non Metallic |
| Service |
Standard |
| Type of Device |
Plug |
| Amperage |
32A International |
| Voltage |
220/280-240/415 |
| Poles and Wires |
4 Pole, 5 Wire Grounding |
| Color |
|
| Configuration |
UL 1686 C2, IEC 309-2, Clock
Position 6, Watertight. |
| Dimension A |
8.54" (216.9) |
| Dimension B |
4.02" (102.0) |
| Cord Grip Range |
.500"-1.450" (17.8-36.8) |
| Housing Material |
Zytel ST801 Nylon. |
| Locking Ring Material |
Zytel ST901 Nylon or Rynite
SST35. |
| Contact Carrier
Material |
High-Impact Thermoset. |
| Retainer Material |
High-Impact Thermoset. |
| Ground, Phase Pins
Material |
Brass. |
| Terminal Screw Material |
Stainless Steel (300 Series).
|
| Assembly Screw Material |
Stainless Steel (300 Series).
|
| Gaskets Material |
Solid Neoprene. |
| Gland Material |
Solid Neoprene. |
| Sealing Gasket Material |
Solid Neoprene. |
| Cord Clamp Material |
Zytel ST901 Nylon or Rynite
SST35 |
| Clamp Nut Material |
Nickel-plated Brass. |
| Gland Cap Material |
Zytel ST901 Nylon or Rynite
SST35. |
| Gland Clamp Screws
Material |
Stainless Steel (300 Series).
|
| Cord Clamp Screws
Material |
Stainless Steel (300 Series).
|
| Dielectric Withstand
Voltage |
3000V AC |
| Current Interrupting |
Certified for current
interrupting at full rated current. |
| Temperature Rise |
Max. 30°C temperature rise at
full rated current after 50 cycles of overload at 150% of rated
current at a power factor of .75. |
| Endurance |
5,000 connect and disconnect
cycles at full rated current and voltage. |
| Impact Resistance |
Per CSA C22.2 No. 182.1,
Paragraph 7.4.2. |
| Cord Grip Cable
Retention |
Per CSA C22.2 No. 182.1,
Paragraph 7.3.1 to 7.3.4. |
| Cord Accommodation |
Round portable service cords of
diameters commensurate with the device rating as defined in UL
Standard 62, CSA C22.2 No. 49 and the harmonized European
Standards. |
| Terminal Identification |
Terminals identified in
accordance with North American and IEC convention and UL 498 (L1,
L2, L3, N GR). |
| Product Identification |
Identification and ratings are
a permanent part of the device housing. |
| Moisture Resistance |
Watertight per IEC 309-1, 18.
(b) IP67. |
| Flammability |
HB or better per UL 94 or CSA
C22.2 No.0.6. |
| Operating Temperatures |
Maximum Continuous 75° C
Minimum - 40°C w/o impact. |
| UV Resistance |
All materials are UV stabilized
|