| Hubbell Wiring Device-Kellems Product
Specifications |
| Product Type |
Watertight IEC 309 |
| Material |
Non Metallic |
| Service |
Standard |
| Type of Device |
Flanged Inlets |
| Amperage |
125A International |
| Voltage |
220-240 |
| Poles and Wires |
2 Pole, 3 Wire Grounding |
| Color |
|
| Configuration |
UL 1686 C2, IEC 309-2, Clock
Position 6, Watertight. |
| Dimension A |
4.53" (115) |
| Dimension B |
3.44" (87.5) |
| Dimension C |
1.95" (49.5) |
| Dimension D |
3.94" (100.0) |
| Dimension E |
5.50" (139.7) |
| Dimension F |
4.88" (124.0) |
| Housing Material |
Zytel® 101 Nylon. |
| Locking Ring Material |
Zytel ST901 Nylon or Rynite®
SST35. |
| Mounting Flange
Material |
Zytel 101 Nylon. |
| Mounting Screw Material |
Stainless Steel (300 Series).
|
| Contact Carrier
Material |
High-Impact Thermoset. |
| Retainer Material |
High-Impact Thermoset. |
| Ground, Phase Pins
Material |
Brass. |
| Terminal Screw Material |
Stainless Steel (300 Series).
|
| Assembly Screw Material |
Stainless Steel (300 Series).
|
| Gaskets Material |
Solid Neoprene. |
| Sealing Gasket Material |
Solid Neoprene. |
| Dielectric Withstand
Voltage |
3000V AC |
| Current Interrupting |
Not for current rupture |
| Temperature Rise |
Max. 30°C temperature rise at
full rated current. |
| Endurance |
5,000 connect and disconnect
cycles at full rated current and voltage. |
| Impact Resistance |
Per CSA C22.2 No. 182.1,
Paragraph 7.4.2. |
| Terminal Identification |
Terminals identified in
accordance with North American and IEC convention and UL 498 (L1,
L2, L3, N GR). |
| Product Identification |
Identification and ratings are
a permanent part of the device housing. |
| Moisture Resistance |
Watertight per IEC 309-1, 18.
(b) IP67. |
| Flammability |
HB or better per UL 94 or CSA
C22.2 No.0.6. |
| Operating Temperatures |
Maximum Continuous 75° C
Minimum - 40°C w/o impact. |
| UV Resistance |
All materials are UV stabilized
|
| Certifications |
| CSA Certified File LR280C for Plugs,
Connectors and Inlets and LR285C for Receptacle CSA Standard C22.2
No. 182.2 |
| Watertight Application Guide |
| Industry |
Watertight |
| Agriculture |
Outdoor for fans, heaters, pumps, etc. |
| Chemical Processing |
Where subject to water, corrosion and rough use. |
| Construction |
Outdoors subject to severe weather conditions. |
| Entertainment |
Outdoors subject to severe weather. |
| Food Processing |
Where subject to water, corrosion and rough use. |
| Food Service |
Areas subject to wash downs & heavy cleaning. |
| Light Manufacturing |
Subjected to cleaning, solvents & chemicals. |
| Manufacturing |
Where subject to water, corrosion and rough use (i.e.,
mills). |
| Military |
Outdoor construction or maintenance subject to severe
weather. | |
|