Product Data Sheet    

PT7FSDBRS2

All Brass: Includes brushed brass carpet flange and matching brass duplex flap cover. Equipped with a pre-wired Hubbell HBL5352 black receptacle and two brass low-voltage knockouts.

Hubbell Wiring Device-Kellems Product Specifications
 Poke-Through Style  
 Type  2 Outlet Flush
 Item  Complete Unit
 Core Hole Size  3"
 Flush Service Type  Duplex Receptacle with Low Voltage Option
 Amperage  20
 Color  
 Fire Rating  For use in 1, 1 1/2, 2, 3, or 4 hour rated unprotected reinforced concrete floors or in 1, 2, or 3 hour rated floors employing steel floor units and concrete topping (D900 Series design).
 Floor Thickness Range  2 1/4" (over metal deck) to 7" (57.2mm to 177.8mm).
 UL Installation Spacing  Minimum of 2 feet O.C. and not more than one unit per each 65 sq. ft. of floor area in each span.
 Cored Hole  3" (76.2) diameter
 Receptacle  Hubbell #HBL5352BK black; NEMA 5-20R; 20A 125V; prewired
 Power Conductors  #12 AWG THHN stranded copper
 Device Cover and Flaps Material  Brass
 Carpet Flanges Material  Solid brass, brushed and lacquered
 Power Conduit Tubes Material  3/4" EMT
 Junction Box  13.0 cubic inches; eight 3/4" knock outs
 Outlet Box UL Listing  E31999
 Fire Resistance UL Listing  R8429
 Style  Flush




 

Hubbell Wiring Device-Kellems