| Hubbell Wiring Device-Kellems Product
Specifications |
| Poke-Through Style |
|
| Type |
2 Outlet Flush |
| Item |
Complete Unit |
| Core Hole Size |
3" |
| Flush Service Type |
Duplex Receptacle with Low
Voltage Option |
| Amperage |
20 |
| Color |
|
| Fire Rating |
For use in 1, 1 1/2, 2, 3, or 4
hour rated unprotected reinforced concrete floors or in 1, 2, or 3
hour rated floors employing steel floor units and concrete topping
(D900 Series design). |
| Floor Thickness Range |
2 1/4" (over metal deck) to 7"
(57.2mm to 177.8mm). |
| UL Installation Spacing |
Minimum of 2 feet O.C. and not
more than one unit per each 65 sq. ft. of floor area in each span.
|
| Cored Hole |
3" (76.2) diameter |
| Receptacle |
Hubbell #HBL5352BK black; NEMA
5-20R; 20A 125V; prewired |
| Power Conductors |
#12 AWG THHN stranded copper
|
| Device Cover and Flaps
Material |
Brass |
| Carpet Flanges Material |
Solid brass, brushed and
lacquered |
| Power Conduit Tubes
Material |
3/4" EMT |
| Junction Box |
13.0 cubic inches; eight 3/4"
knock outs |
| Outlet Box UL Listing |
E31999 |
| Fire Resistance UL
Listing |
R8429 |
| Style |
Flush |